Datasheet| Operating voltage type | 1-/2-/3-phase |
| Operating voltage | 95...240 VAC, 110...340 VDC |
| Rated measurement input voltage | 400/690 VAC |
| Rated measurement input current | 5 A |
| Measurement input | Transformer |
| Assembly type | Panel mount, front-side |
| Displays | 3 x 4-digit |
| Display type | LCD, backlit |
| Output | Digital |
| Protection rating | IP 65 front panel |
| Operating temperature | -10...+55 °C |
| Decimal places | 2 |
| Dimensions W x H x D | 96 x 96 x 56 mm |
| Front panel cutout | 92 x 92 mm |
| Max. measurement input current | 10 A |
| Frequency | 45...65 Hz |
| Operating temperature max. | +55 °C |
| Operating temperature min. | -10 °C |
| Width | 96 mm |
| Height | 96 mm |
| Depth | 56 mm |
| Measurement accuracy | Class 0.5S @ IEC 62053-22 |